Construction Tolerances: Construction Tolerances

Bed joint tolerances
Bed joint tolerances

Let’s face it, the perfect masonry wall probably hasn’t been built. But how good is good enough, when constructing a masonry wall or column? Fortunately, the Masonry Building Code contains specifications (TMS 602) that provide construction tolerances that are well recognized within the industry. Keep in mind that these are minimum requirements and that project specifications may require tighter tolerances. Also note that these tolerances are not applicable to either anchored or adhered veneer.

A logical place to start is the bottom of the wall and the applicable tolerance here is that the bed joint for the first course be at least ¼ inch thick but not more than ¾ inch when the masonry is ungrouted or partially grouted. The maximum first course bed joint thickness is increased to 1 ¼ inch when the first course if fully grouted and supported by a concrete foundation. Unless otherwise noted, bed and head joints are to be 3/8 inch (except for the first course).

The allowable variation in bed joint thickness between masonry courses is ± 1/8 inch and bed joints are to be within ± ¼ inch of level in 10 feet with a maximum out of level of ½ inch in 10 feet. Note that these apply to CMU and clay masonry construction and that there are other requirements for glass block and autoclaved aerated concrete (AAC) masonry.

As for overall tolerances for walls, the top surface of load-bearing walls must be within ± ¼ inch of level in 10 feet with a maximum out of level of ½ inch in 10 feet. Plumb tolerances are similar with a permissible variation from plumb of ± ¼ inch in 10 feet, ± 3/8 in 20 feet and ± ½ inch maximum. Walls are to be true to a line with the same tolerances as for plumb.

Plumb tolerance in walls
Plumb tolerance in walls

Load-bearing columns must be within ± ½ inch of plumb from top to bottom and non-load-bearing columns must be within ± ¾ inch of plumb over their height.

Location of masonry elements in plan must be within ± ½ inch in 20 feet with a maximum variation of ± ¾ inch. Similarly, masonry elements indicated in elevation should be within ± ¼ inch in the story height with a maximum variation of ± ¾ inch.

Tolerances in elevation
Tolerances in elevation

Lastly, any aesthetic issues, such as minor chips or cracks, should not be visible when viewed from 20 feet under diffuse lighting. This requirement is not from the Masonry Building Code but is given in ASTM standard specifications for loadbearing CMU (ASTM C90) and for loadbearing brick masonry (ASTM C216). Again, check the project specifications for any additional requirements.

Helical Beaming: Strengthening Masonry from the Inside Out
February 2026

In the world of masonry restoration and retrofit, the goal is always the same: preserve the character and craftsmanship of historic structures while ensuring their long-term stability. But anyone who has worked on century-old brick or stone buildings know

A Practical Guide to Modern Masonry Restoration
February 2026

THE MYTH: Masonry Lasts Forever It’s strong, yes, but movement, moisture, and time still take their toll. Common Causes Why Masonry Fails: - Differential movement - Thermal expansion & contraction - Moisture intrusion & freeze–thaw - Corrosion of steel

The 2026 MCAA Annual Online Auction
February 2026

The Mason Contractors Association of America is thrilled to announce the 2026 Annual Online Auction, the masonry industry’s premier event for scoring the best equipment at a fraction of costs. Whether you are looking to expand your equipment stockpile or

CMU Partitions: How Much Reinforcement Is Actually Required?
February 2026

Walk onto almost any job site and you’ll find masons laying out interior partitions much the same way they did decades ago. The work looks straightforward: stack the units, strike clean joints, and keep the wall plumb. And the function of these partitions