Construction Tolerances: Construction Tolerances

Bed joint tolerances
Bed joint tolerances

Let’s face it, the perfect masonry wall probably hasn’t been built. But how good is good enough, when constructing a masonry wall or column? Fortunately, the Masonry Building Code contains specifications (TMS 602) that provide construction tolerances that are well recognized within the industry. Keep in mind that these are minimum requirements and that project specifications may require tighter tolerances. Also note that these tolerances are not applicable to either anchored or adhered veneer.

A logical place to start is the bottom of the wall and the applicable tolerance here is that the bed joint for the first course be at least ¼ inch thick but not more than ¾ inch when the masonry is ungrouted or partially grouted. The maximum first course bed joint thickness is increased to 1 ¼ inch when the first course if fully grouted and supported by a concrete foundation. Unless otherwise noted, bed and head joints are to be 3/8 inch (except for the first course).

The allowable variation in bed joint thickness between masonry courses is ± 1/8 inch and bed joints are to be within ± ¼ inch of level in 10 feet with a maximum out of level of ½ inch in 10 feet. Note that these apply to CMU and clay masonry construction and that there are other requirements for glass block and autoclaved aerated concrete (AAC) masonry.

As for overall tolerances for walls, the top surface of load-bearing walls must be within ± ¼ inch of level in 10 feet with a maximum out of level of ½ inch in 10 feet. Plumb tolerances are similar with a permissible variation from plumb of ± ¼ inch in 10 feet, ± 3/8 in 20 feet and ± ½ inch maximum. Walls are to be true to a line with the same tolerances as for plumb.

Plumb tolerance in walls
Plumb tolerance in walls

Load-bearing columns must be within ± ½ inch of plumb from top to bottom and non-load-bearing columns must be within ± ¾ inch of plumb over their height.

Location of masonry elements in plan must be within ± ½ inch in 20 feet with a maximum variation of ± ¾ inch. Similarly, masonry elements indicated in elevation should be within ± ¼ inch in the story height with a maximum variation of ± ¾ inch.

Tolerances in elevation
Tolerances in elevation

Lastly, any aesthetic issues, such as minor chips or cracks, should not be visible when viewed from 20 feet under diffuse lighting. This requirement is not from the Masonry Building Code but is given in ASTM standard specifications for loadbearing CMU (ASTM C90) and for loadbearing brick masonry (ASTM C216). Again, check the project specifications for any additional requirements.

There’s the Typical Way to Brace a Wall. And Then There’s a Better Way.
May 2026

Wall bracing is one of the most important safety considerations on any masonry jobsite, yet it is often treated as a task that happens after the wall is built. Crews return, equipment is brought in, and time is set aside to secure walls that have already

Why Coordinated Material Supply Matters in Modern Masonry Construction
May 2026

The Advantages of Single-Source Supply in Modern Masonry Construction Masonry construction has evolved significantly over the past several decades. While brick and mortar remain the defining elements of masonry walls, the assemblies behind them have beco

Remembering Harry McGraw
May 2026

The masonry industry has lost one of its great teachers and craftsmen with the passing of Harry Edward McGraw, who died April 26, 2026, in Houston, Texas, at the age of 93.

The Gary Joyner Masonry Scholarship: Investing In The Future
May 2026

The North Carolina Masonry Contractors Association (NCMCA) Eastern Chapter has launched the Gary Joyner Masonry Scholarship at Pitt Community College in Greenville, North Carolina. The annual award honors one of the trade's most influential figures while