Construction Tolerances: Construction Tolerances

Bed joint tolerances
Bed joint tolerances

Let’s face it, the perfect masonry wall probably hasn’t been built. But how good is good enough, when constructing a masonry wall or column? Fortunately, the Masonry Building Code contains specifications (TMS 602) that provide construction tolerances that are well recognized within the industry. Keep in mind that these are minimum requirements and that project specifications may require tighter tolerances. Also note that these tolerances are not applicable to either anchored or adhered veneer.

A logical place to start is the bottom of the wall and the applicable tolerance here is that the bed joint for the first course be at least ¼ inch thick but not more than ¾ inch when the masonry is ungrouted or partially grouted. The maximum first course bed joint thickness is increased to 1 ¼ inch when the first course if fully grouted and supported by a concrete foundation. Unless otherwise noted, bed and head joints are to be 3/8 inch (except for the first course).

The allowable variation in bed joint thickness between masonry courses is ± 1/8 inch and bed joints are to be within ± ¼ inch of level in 10 feet with a maximum out of level of ½ inch in 10 feet. Note that these apply to CMU and clay masonry construction and that there are other requirements for glass block and autoclaved aerated concrete (AAC) masonry.

As for overall tolerances for walls, the top surface of load-bearing walls must be within ± ¼ inch of level in 10 feet with a maximum out of level of ½ inch in 10 feet. Plumb tolerances are similar with a permissible variation from plumb of ± ¼ inch in 10 feet, ± 3/8 in 20 feet and ± ½ inch maximum. Walls are to be true to a line with the same tolerances as for plumb.

Plumb tolerance in walls
Plumb tolerance in walls

Load-bearing columns must be within ± ½ inch of plumb from top to bottom and non-load-bearing columns must be within ± ¾ inch of plumb over their height.

Location of masonry elements in plan must be within ± ½ inch in 20 feet with a maximum variation of ± ¾ inch. Similarly, masonry elements indicated in elevation should be within ± ¼ inch in the story height with a maximum variation of ± ¾ inch.

Tolerances in elevation
Tolerances in elevation

Lastly, any aesthetic issues, such as minor chips or cracks, should not be visible when viewed from 20 feet under diffuse lighting. This requirement is not from the Masonry Building Code but is given in ASTM standard specifications for loadbearing CMU (ASTM C90) and for loadbearing brick masonry (ASTM C216). Again, check the project specifications for any additional requirements.

Remembering Paul Odom
December 2025

The masonry industry lost a true titan and a dedicated leader with the passing of Paul Odom. Known for his unwavering commitment to his craft and his community, Paul leaves behind a legacy defined not just by the structures he helped build.

Managing the Modern Jobsite: How MSV Helps Crews Do More with Less in 2026
December 2025

On today’s jobsites, efficiency is becoming as essential as craftsmanship. Crews are working with fewer hands, tighter schedules, and greater pressure to deliver high-quality results without increasing costs. It’s a reality affecting everything from resid

A Free Resource for Contractors: The Block Design Collective
December 2025

The Concrete Masonry Checkoff has launched the Block Design Collective (BDC), a national resource that provides fast, reliable guidance for anyone designing or building with concrete masonry. For contractors, the benefit is straightforward: better informa

The Hidden Forces That Build America: Arching Action and the Tools We Trust
December 2025

Most people at World of Concrete can identify a CMU block from 50 feet away. Some can even smell Type S mortar curing from across the hall. But mention the phrase “arching action,” and you will see a surprising number of boots shift and eyes drift toward