Construction Tolerances: Construction Tolerances

Bed joint tolerances
Bed joint tolerances

Let’s face it, the perfect masonry wall probably hasn’t been built. But how good is good enough, when constructing a masonry wall or column? Fortunately, the Masonry Building Code contains specifications (TMS 602) that provide construction tolerances that are well recognized within the industry. Keep in mind that these are minimum requirements and that project specifications may require tighter tolerances. Also note that these tolerances are not applicable to either anchored or adhered veneer.

A logical place to start is the bottom of the wall and the applicable tolerance here is that the bed joint for the first course be at least ¼ inch thick but not more than ¾ inch when the masonry is ungrouted or partially grouted. The maximum first course bed joint thickness is increased to 1 ¼ inch when the first course if fully grouted and supported by a concrete foundation. Unless otherwise noted, bed and head joints are to be 3/8 inch (except for the first course).

The allowable variation in bed joint thickness between masonry courses is ± 1/8 inch and bed joints are to be within ± ¼ inch of level in 10 feet with a maximum out of level of ½ inch in 10 feet. Note that these apply to CMU and clay masonry construction and that there are other requirements for glass block and autoclaved aerated concrete (AAC) masonry.

As for overall tolerances for walls, the top surface of load-bearing walls must be within ± ¼ inch of level in 10 feet with a maximum out of level of ½ inch in 10 feet. Plumb tolerances are similar with a permissible variation from plumb of ± ¼ inch in 10 feet, ± 3/8 in 20 feet and ± ½ inch maximum. Walls are to be true to a line with the same tolerances as for plumb.

Plumb tolerance in walls
Plumb tolerance in walls

Load-bearing columns must be within ± ½ inch of plumb from top to bottom and non-load-bearing columns must be within ± ¾ inch of plumb over their height.

Location of masonry elements in plan must be within ± ½ inch in 20 feet with a maximum variation of ± ¾ inch. Similarly, masonry elements indicated in elevation should be within ± ¼ inch in the story height with a maximum variation of ± ¾ inch.

Tolerances in elevation
Tolerances in elevation

Lastly, any aesthetic issues, such as minor chips or cracks, should not be visible when viewed from 20 feet under diffuse lighting. This requirement is not from the Masonry Building Code but is given in ASTM standard specifications for loadbearing CMU (ASTM C90) and for loadbearing brick masonry (ASTM C216). Again, check the project specifications for any additional requirements.

Hanover Architectural Products Renews as a Gold in the 2026 MAP
October 2025

The Mason Contractors Association of America (MCAA) is excited to announce that Hanover Architectural Products will be renewing its Gold partnership in the 2026 Masonry Alliance Program.

GEORGE Turns One: MCAA's Purpose-Built AI Platform Processing 36 Million Tokens Per Month
October 2025

On the heels of the MCAA joining the White House’s AI In Education Task Force, the Association’s GEORGE AI completed its first year in a public, open beta. From its inception nearly four years ago, GEORGE had a singular mission.

MARSHALLTOWN Continues as a Silver in the 2026 MAP
October 2025

The Mason Contractors Association of America (MCAA) is pleased to announce that MARSHALLTOWN will continue its Silver partnership in the 2026 Masonry Alliance Program.

2026 World Of Concrete Judge Registration Now Open
October 2025

Following the MCAA's recent announcement opening judge registration for the World of Concrete competitions, SkillsUSA and the Fastest Trowel on the Block, we wanted to remind everyone of our competitions’ judging stipulation. To ensure the integrity and f