Construction Tolerances: Construction Tolerances

Bed joint tolerances
Bed joint tolerances

Let’s face it, the perfect masonry wall probably hasn’t been built. But how good is good enough, when constructing a masonry wall or column? Fortunately, the Masonry Building Code contains specifications (TMS 602) that provide construction tolerances that are well recognized within the industry. Keep in mind that these are minimum requirements and that project specifications may require tighter tolerances. Also note that these tolerances are not applicable to either anchored or adhered veneer.

A logical place to start is the bottom of the wall and the applicable tolerance here is that the bed joint for the first course be at least ¼ inch thick but not more than ¾ inch when the masonry is ungrouted or partially grouted. The maximum first course bed joint thickness is increased to 1 ¼ inch when the first course if fully grouted and supported by a concrete foundation. Unless otherwise noted, bed and head joints are to be 3/8 inch (except for the first course).

The allowable variation in bed joint thickness between masonry courses is ± 1/8 inch and bed joints are to be within ± ¼ inch of level in 10 feet with a maximum out of level of ½ inch in 10 feet. Note that these apply to CMU and clay masonry construction and that there are other requirements for glass block and autoclaved aerated concrete (AAC) masonry.

As for overall tolerances for walls, the top surface of load-bearing walls must be within ± ¼ inch of level in 10 feet with a maximum out of level of ½ inch in 10 feet. Plumb tolerances are similar with a permissible variation from plumb of ± ¼ inch in 10 feet, ± 3/8 in 20 feet and ± ½ inch maximum. Walls are to be true to a line with the same tolerances as for plumb.

Plumb tolerance in walls
Plumb tolerance in walls

Load-bearing columns must be within ± ½ inch of plumb from top to bottom and non-load-bearing columns must be within ± ¾ inch of plumb over their height.

Location of masonry elements in plan must be within ± ½ inch in 20 feet with a maximum variation of ± ¾ inch. Similarly, masonry elements indicated in elevation should be within ± ¼ inch in the story height with a maximum variation of ± ¾ inch.

Tolerances in elevation
Tolerances in elevation

Lastly, any aesthetic issues, such as minor chips or cracks, should not be visible when viewed from 20 feet under diffuse lighting. This requirement is not from the Masonry Building Code but is given in ASTM standard specifications for loadbearing CMU (ASTM C90) and for loadbearing brick masonry (ASTM C216). Again, check the project specifications for any additional requirements.

About: Technical Talks
Natural Stone Ordering: Details Matter Before the Job Starts
October 2026

A lot of problems on a stone job can be traced back to the order. I’m on the supplier side, so I see it regularly. A mason can do everything right in the field and still end up fighting a job because the wrong material was ordered, quantities were off, c

Dust Mitigation in Masonry: Practical Strategies for Safer Job Sites
October 2026

Every day, masonry professionals cut block, grind mortar joints, core drill, mix dry materials, and demolish existing structures. These tasks are fundamental to the trade, but they also generate dust. While dust may seem like an unavoidable part of the jo

What Does That Marking Actually Mean?: Understanding the Standards Behind Your PPE
October 2026

Walk onto almost any masonry project, and you will see a variety of markings on personal protective equipment: Z87+, Type I, Type II, Class E, ANSI, and others. We recognize many of these markings and know they are important, but understanding exactly wha

TERRA Footwear Renews as a Silver Partner in 2027
October 2026

The Mason Contractors Association of America (MCAA) is pleased to share that TERRA Footwear will renew as a Silver Partner in the 2027 Masonry Alliance Program.