Construction Tolerances: Construction Tolerances

Bed joint tolerances
Bed joint tolerances

Let’s face it, the perfect masonry wall probably hasn’t been built. But how good is good enough, when constructing a masonry wall or column? Fortunately, the Masonry Building Code contains specifications (TMS 602) that provide construction tolerances that are well recognized within the industry. Keep in mind that these are minimum requirements and that project specifications may require tighter tolerances. Also note that these tolerances are not applicable to either anchored or adhered veneer.

A logical place to start is the bottom of the wall and the applicable tolerance here is that the bed joint for the first course be at least ¼ inch thick but not more than ¾ inch when the masonry is ungrouted or partially grouted. The maximum first course bed joint thickness is increased to 1 ¼ inch when the first course if fully grouted and supported by a concrete foundation. Unless otherwise noted, bed and head joints are to be 3/8 inch (except for the first course).

The allowable variation in bed joint thickness between masonry courses is ± 1/8 inch and bed joints are to be within ± ¼ inch of level in 10 feet with a maximum out of level of ½ inch in 10 feet. Note that these apply to CMU and clay masonry construction and that there are other requirements for glass block and autoclaved aerated concrete (AAC) masonry.

As for overall tolerances for walls, the top surface of load-bearing walls must be within ± ¼ inch of level in 10 feet with a maximum out of level of ½ inch in 10 feet. Plumb tolerances are similar with a permissible variation from plumb of ± ¼ inch in 10 feet, ± 3/8 in 20 feet and ± ½ inch maximum. Walls are to be true to a line with the same tolerances as for plumb.

Plumb tolerance in walls
Plumb tolerance in walls

Load-bearing columns must be within ± ½ inch of plumb from top to bottom and non-load-bearing columns must be within ± ¾ inch of plumb over their height.

Location of masonry elements in plan must be within ± ½ inch in 20 feet with a maximum variation of ± ¾ inch. Similarly, masonry elements indicated in elevation should be within ± ¼ inch in the story height with a maximum variation of ± ¾ inch.

Tolerances in elevation
Tolerances in elevation

Lastly, any aesthetic issues, such as minor chips or cracks, should not be visible when viewed from 20 feet under diffuse lighting. This requirement is not from the Masonry Building Code but is given in ASTM standard specifications for loadbearing CMU (ASTM C90) and for loadbearing brick masonry (ASTM C216). Again, check the project specifications for any additional requirements.

The Behind-the-Wall Secrets Every Mason Already Knows (But Some Ignore)
March 2026

You’ve been around long enough to know this already: stone doesn’t fail on the face; it fails behind the wall. You can lay the prettiest veneer in the county, but if the prep is junk, that wall’s gonna start telling on you after a couple of winters. Manu

From the Mound to the Mortar: Jon Rauch’s Tall Order in the Masonry Industry
March 2026

In the record books of Major League Baseball, Jon Rauch is a literal giant. At 6 feet, 11 inches, he remains the tallest player to ever step onto a Big League mound. But today, the Olympic Gold Medalist and 11-season MLB veteran isn’t looking for a strike

Case Study: The Scoop
March 2026

Leading UK architecture firm, Corstorphine & Wright, has announced the completion of ‘The Scoop’, a unique concave office building in Southwark, London. The innovative design reuses an existing building and integrates a conical cut-out façade in white gla

Executing Color-Driven Designs Without Compromising Craftsmanship
March 2026

On today’s jobsites, masonry contractors are being asked to do more than install manufactured stone veneer (MSV). They’re being asked to interpret design trends and execute them with precision. Homeowners arrive with curated Pinterest boards. Designers r