Construction Tolerances: Construction Tolerances

Bed joint tolerances
Bed joint tolerances

Let’s face it, the perfect masonry wall probably hasn’t been built. But how good is good enough, when constructing a masonry wall or column? Fortunately, the Masonry Building Code contains specifications (TMS 602) that provide construction tolerances that are well recognized within the industry. Keep in mind that these are minimum requirements and that project specifications may require tighter tolerances. Also note that these tolerances are not applicable to either anchored or adhered veneer.

A logical place to start is the bottom of the wall and the applicable tolerance here is that the bed joint for the first course be at least ¼ inch thick but not more than ¾ inch when the masonry is ungrouted or partially grouted. The maximum first course bed joint thickness is increased to 1 ¼ inch when the first course if fully grouted and supported by a concrete foundation. Unless otherwise noted, bed and head joints are to be 3/8 inch (except for the first course).

The allowable variation in bed joint thickness between masonry courses is ± 1/8 inch and bed joints are to be within ± ¼ inch of level in 10 feet with a maximum out of level of ½ inch in 10 feet. Note that these apply to CMU and clay masonry construction and that there are other requirements for glass block and autoclaved aerated concrete (AAC) masonry.

As for overall tolerances for walls, the top surface of load-bearing walls must be within ± ¼ inch of level in 10 feet with a maximum out of level of ½ inch in 10 feet. Plumb tolerances are similar with a permissible variation from plumb of ± ¼ inch in 10 feet, ± 3/8 in 20 feet and ± ½ inch maximum. Walls are to be true to a line with the same tolerances as for plumb.

Plumb tolerance in walls
Plumb tolerance in walls

Load-bearing columns must be within ± ½ inch of plumb from top to bottom and non-load-bearing columns must be within ± ¾ inch of plumb over their height.

Location of masonry elements in plan must be within ± ½ inch in 20 feet with a maximum variation of ± ¾ inch. Similarly, masonry elements indicated in elevation should be within ± ¼ inch in the story height with a maximum variation of ± ¾ inch.

Tolerances in elevation
Tolerances in elevation

Lastly, any aesthetic issues, such as minor chips or cracks, should not be visible when viewed from 20 feet under diffuse lighting. This requirement is not from the Masonry Building Code but is given in ASTM standard specifications for loadbearing CMU (ASTM C90) and for loadbearing brick masonry (ASTM C216). Again, check the project specifications for any additional requirements.

About: Technical Talks
The Craft of Brick Repair: The Difference Between a Coverup and a Solution
June 2026

More often than not, you can walk up to a wall, observe its condition, and get an entire timeline story. How it was built, how footers were set, and where water is routed. After years in the field, I’ve come to understand that brick repair isn’t maintenan

The Benefits of Concealed Lintel Systems in Modern Masonry
June 2026

When looking at iconic structures built throughout history, one of the most recognizable architectural elements is the masonry arch. These arches are not only aesthetically and visually pleasing but also serve as an engineering solution for structural sta

What’s New With CMU: A Closer Look From Ken Rathbun
June 2026

Anyone who’s spending time around CMU jobs today can see the shift. Concrete masonry isn’t just the backup wall; it is the finish on more projects. Thanks in part to the CMU check-off program and a broader focus on design and education, architects and own

Brick & Masonry Aesthetics: Managing Color, Consistency, and Architectural Expectations
June 2026

Brick and masonry remain among the most admired architectural materials in the world because of their natural beauty and authenticity. Masonry possesses depth, variation, texture, permanence, and character that synthetic cladding systems often struggle to