Construction Tolerances: Construction Tolerances

Bed joint tolerances
Bed joint tolerances

Let’s face it, the perfect masonry wall probably hasn’t been built. But how good is good enough, when constructing a masonry wall or column? Fortunately, the Masonry Building Code contains specifications (TMS 602) that provide construction tolerances that are well recognized within the industry. Keep in mind that these are minimum requirements and that project specifications may require tighter tolerances. Also note that these tolerances are not applicable to either anchored or adhered veneer.

A logical place to start is the bottom of the wall and the applicable tolerance here is that the bed joint for the first course be at least ¼ inch thick but not more than ¾ inch when the masonry is ungrouted or partially grouted. The maximum first course bed joint thickness is increased to 1 ¼ inch when the first course if fully grouted and supported by a concrete foundation. Unless otherwise noted, bed and head joints are to be 3/8 inch (except for the first course).

The allowable variation in bed joint thickness between masonry courses is ± 1/8 inch and bed joints are to be within ± ¼ inch of level in 10 feet with a maximum out of level of ½ inch in 10 feet. Note that these apply to CMU and clay masonry construction and that there are other requirements for glass block and autoclaved aerated concrete (AAC) masonry.

As for overall tolerances for walls, the top surface of load-bearing walls must be within ± ¼ inch of level in 10 feet with a maximum out of level of ½ inch in 10 feet. Plumb tolerances are similar with a permissible variation from plumb of ± ¼ inch in 10 feet, ± 3/8 in 20 feet and ± ½ inch maximum. Walls are to be true to a line with the same tolerances as for plumb.

Plumb tolerance in walls
Plumb tolerance in walls

Load-bearing columns must be within ± ½ inch of plumb from top to bottom and non-load-bearing columns must be within ± ¾ inch of plumb over their height.

Location of masonry elements in plan must be within ± ½ inch in 20 feet with a maximum variation of ± ¾ inch. Similarly, masonry elements indicated in elevation should be within ± ¼ inch in the story height with a maximum variation of ± ¾ inch.

Tolerances in elevation
Tolerances in elevation

Lastly, any aesthetic issues, such as minor chips or cracks, should not be visible when viewed from 20 feet under diffuse lighting. This requirement is not from the Masonry Building Code but is given in ASTM standard specifications for loadbearing CMU (ASTM C90) and for loadbearing brick masonry (ASTM C216). Again, check the project specifications for any additional requirements.

Chairman's Message: REFLECTIONS SPANNING SEVENTY-FIVE YEARS
September 2025

MCAA has been posting lots of wonderful old photos from decades of records as we celebrate our 75th Anniversary. Many of these photos are black and white and show people at our MCAA events with men wearing suits and ties while the women wore dressy gowns

Business Building: What Are You Doing To Develop Future Leaders?
September 2025

When I ask my coaching clients if they have anyone in their construction company who could potentially move up from field superintendent to estimator or project manager, the typical answer is “No!” The same answer is usually given when asked if they have

Building More: Smoke Signals or Fire Extinguishers
September 2025

Ever watch a hot-potato game break out on your jobsite? It usually starts small. Somebody spots a crooked door frame, mutters, “I’ll make a note,” and flicks the issue to the next trade like it’s radioactive. By the time that frame comes back around, dryw

MASONRY STRONG Podcast, Episode 27 Recap: Rob McKay, Chief Operating Officer at Instone
September 2025

On this episode of the MASONRY STRONG Podcast, Rob McKay from Instone joins the show to talk about his story as well as the processes and procedures of manufacturing natural stone. Getting Started in Masonry: Rob’s Story Rob entered the masonry field by